EquipmentReference size s_refReference cost c_ref, USDEquipment exponent n_eqpInstalled exponent n_instMultiple at s_ref icm_refValid rangeEvidence
High-temperature industrial heat pumpMWthheat delivered at sink temperature, NOT electrical inputNot published — regression pending — DEA Technology Data catalogue treated as licensed on client instruction, 4 September 2026 – the legal block is CLOSED. What remains is a DATA block, which was always the real one. No capacity-cost points have been extracted and no regression exists, so there is nothing to publish. One gate before this can be enabled: the regression run and passing the quality bar of 14-exponent-register.md section 3. Register v0.2 task. Record the licence document reference against the dea-tech source row before the first published value. Do NOT substitute a proxy – Not published
Electric boilerMWthsteam or hot water raisedNot published — regression pending — DEA Technology Data catalogue treated as licensed on client instruction, 4 September 2026 – the legal block is CLOSED. What remains is a DATA block, which was always the real one. No capacity-cost points have been extracted and no regression exists, so there is nothing to publish. One gate before this can be enabled: the regression run and passing the quality bar of 14-exponent-register.md section 3. Register v0.2 task. Record the licence document reference against the dea-tech source row before the first published value. Do NOT substitute a proxy – Not published
Package steam boiler (fossil comparator)kg/hlb/hrA285C, 250 psigIncluded as the comparator an electrification business case is measured against. 50,000 lb/hr ≈ 14.65 MWth at the default enthalpy.22,680 kg/h50,000 lb/hr$236,2760.63180.42482.2134,535.93–136,077.71 kg/h10,000–300,000 lb/hrEstimated
Electric process heater / furnaceMWMMBtu/hrCS tubes, 500 psigFired heater geometry. One of only two entries in the whole register where n_inst EXCEEDS n_eqp — installation scales slightly faster than equipment here. 70 MMBtu/hr = 20.5 MWth.20.5 MW70 MMBtu/hr$918,9250.69060.69791.3292.94–146.53 MW10–500 MMBtu/hrEstimated
Thermal storage tank (partial)m³gallonscone roof, carbon steelPARTIAL SCOPE. Tank shell only. The UI must state that charge/discharge plant, insulation and controls are excluded. 500,000 gal ≈ 61 MWh_th at the defaults.1,893 m³500,000 gallons$192,0750.73810.62881.505189.28–37,854.11 m³50,000–10,000,000 gallonsEstimated

How to cite

Pemspring Energy Solutions, PEICI Heat factor set 2026.1, published 2026-11-01. https://pemspring.com/cost-index/heat/

Published values are in USD and in native units — MWth, lb/hr, MMBtu/hr, gallons — regardless of the unit control above. Cite the native value: it is what the JSON contains and what a later version will be compared against.

Download the factor set as JSON · Open the calculator for this group · Estimating card