Grid & enabling
Units
Capacities shown in metric units.Capacities shown in imperial units. The published JSON is in each equipment record's native units and in USD, and does not change with this control. Unit conversion is exact and reversible; the exponents are dimensionless and identical in both systems.
| Equipment | Reference size s_ref | Reference cost c_ref, USD | Equipment exponent n_eqp | Installed exponent n_inst | Multiple at s_ref icm_ref | Valid range | Evidence |
|---|---|---|---|---|---|---|---|
| Power transformerMVAFOB factory, nameplate MVACRITICAL — n = 0.75 is DOE's WITHIN-VOLTAGE-CLASS exponent on kVA. Fitting a curve straight through the three variant points instead gives 1.44, an apparent diseconomy, because voltage class rises with size and voltage does most of the work. The calculator must scale WITHIN a selected voltage class only, never across them. ICM 1.275 from DOE's stated installed premium of 25–30% over FOB factory.230/115 kV | 300 MVA | $2,000,000 | 0.75 | not published | 1.275 | 75–900 MVA | Estimated |
| 345/138 kV | 500 MVA | $4,000,000 | 0.75 | not published | 1.275 | 75–900 MVA | Estimated |
| 765/138 kV | 750 MVA | $7,500,000 | 0.75 | not published | 1.275 | 75–900 MVA | Estimated |
How to cite
Pemspring Energy Solutions, PEICI Grid & enabling factor set 2026.1, published 2026-11-01. https://pemspring.com/cost-index/grid/
Published values are in USD and in native units — MVA — regardless of the unit control above. Cite the native value: it is what the JSON contains and what a later version will be compared against.
Download the factor set as JSON · Open the calculator for this group · Estimating card