Electrical Infrastructure Burden

Modelled electrical enabling capex per incremental electrical capacity for frozen reference architectures

First reference release · DK_component_reference

157.22

EUR (2020 price level) per kWe

Danish component scope at 2020 EUR price level. NOT a UK or US observed installation cost, and not converted to either.

  • Low — reuse a station with demonstrated spare capacity, 100 m feeder35.23incremental kwe 500 · station count 0 · station mva 0.8 · power factor 0.9 · station rate eur mw 40408.163284 · feeder length m 100 · feeder rate eur m 79.75295385 · service line eur 9640.537061388
  • Base — one new station, 500 m feeder157.22incremental kwe 500 · station count 1 · station mva 0.8 · power factor 0.9 · station rate eur mw 40408.163284 · feeder length m 500 · feeder rate eur m 79.75295385 · service line eur 9640.537061388
  • High — two stations, 1,000 m feeder295.16incremental kwe 500 · station count 2 · station mva 0.8 · power factor 0.9 · station rate eur mw 40408.163284 · feeder length m 1000 · feeder rate eur m 79.75295385 · service line eur 9640.537061388
  • A modelled reference design, not observed project cost.
  • Station cost bundles transformer and switchgear; they must not be charged again elsewhere.
  • The feeder and the source's separate 100 m LV service line are different assets.
  • No upstream reinforcement, utility connection fee, site-specific land, exceptional civils or permitting allowance is included.
  • The two-station case is a cost scenario, not a certified N-1 design.
  • No backcast is supplied: escalating these to earlier years would be an escalation model, not observed historical projects.
0255075100No observations yet — this is not a zero.
This index has no observations yet. The axis and the expected first observation are shown so the commitment is visible; no value is implied.

Definition

What it measures
Modelled electrical enabling capex per incremental electrical capacity for frozen reference architectures
Headline metric
Modelled Electrical Infrastructure Burden, currency per incremental kWe
Supporting metrics
low/base/high architecture; voltage class; transformer/switchgear/cabling components; cost year
Cadence
Quarterly
Panel
Capital & Infrastructure
Primary sources
doe-tsd; doe-xfmr-rule; doe-lpt; PEICI cleared grid factors; published Pemspring design assumptions
Licence position
clear public-domain inputs plus Pemspring assumptions
Release gate
reference architectures, factor IDs, cost scope, exclusions and sensitivity band published

What this does not cover

PROVISIONAL ENGINEERING MODEL, not observed project cost. Civil works, connection charges and site conditions are represented only if explicitly included.